Mill starting procedure :
·        
Clearance from local
operator is to be recorded before starting mill.
·        
Ensure feeder coal on belt
is established.
·        
Ensure  ignition permit is available.
·        
Open bunker outlet &
feeder inlet gate.
·        
Start Mill LOP and observe
lub oil pressure , temperature and flow.
·        
Open CAG ( CADshould be
closed), monitor PA header pressure.
·        
Start Mill and monitor its
current (60-65 Amp normal current).
·        
Open feeder seal air valve
& feeder outletgate.
·        
Open HAG,( HAD should be
closed), monitor PA header pressure.
·        
Observe boiler flame
intensity during mill operation.
 
 