Thermal Power Plant Operation Information guide. Please find here the Stand ard Operating Procedures, Instructions to operate various capacity Thermal power plants in India. This is as per my experience and any abnormality found please refer other sources. Thank you.
Tuesday, September 23, 2025
How to detect Boiler tube lkg in boiler
**Detecting Boiler Tube Leakage in a 210 MW BHEL Boiler at NTPC Dadri**
Boiler tube leakage is a critical issue in power plants like NTPC Dadri’s 210 MW units, which use subcritical BHEL-designed boilers (Combustion Engineering type, commissioned 1991-1994). Early detection minimizes downtime, prevents secondary damage (e.g., to turbine or other tubes), and maintains efficiency. Dadri has a strong record for minimizing tube failures, ranking among NTPC’s top plants, but leaks can still occur due to aging (30+ years), erosion, corrosion, or thermal stresses in high-pressure zones (drum pressure ~155 bar, superheater ~535°C). Below is a detailed guide to detecting boiler tube leaks, tailored to Dadri’s 210 MW BHEL boilers, combining practical methods, NTPC practices, and industry standards.
Strategies to improve efficiency and reduce Heat rate
### Understanding Heat Rate in a 210 MW Boiler at NTPC Dadri
The heat rate of a thermal power plant, including the 210 MW coal-fired units at NTPC Dadri (commissioned between 1991-1994), measures the amount of heat energy (in kcal/kWh) required to generate one kilowatt-hour of electricity. It is inversely proportional to the plant's thermal efficiency: a lower heat rate indicates higher efficiency, reduced fuel consumption (coal), lower emissions, and cost savings. For subcritical 210 MW units like those at Dadri, typical operating heat rates range from 2,300-2,500 kcal/kWh, with opportunities for optimization to below 2,300 kcal/kWh through targeted improvements.
Efficiency improvement in 210 MW boiler
### Understanding Boiler Efficiency in 210 MW BHEL Units
A 210 MW BHEL boiler is typically a coal-fired, subcritical unit common in thermal power stations, where efficiency (often around 80-85% on a higher heating value basis) is influenced by combustion, heat transfer, and auxiliary losses. Improving it can reduce fuel consumption, emissions, and operational costs. Based on thermal audits and BHEL-specific practices, here are proven methods, categorized for clarity. These draw from operational optimizations, retrofits, and maintenance strategies.
Sunday, September 21, 2025
St-1 Vacuum Pulling checklist
CHECK LIST-VACUUM PULLING UNIT: DATE: SL NO ITEM DESCRIPTION STATUS
1. Fill Hot well up to normal level.
2. Vacuum pumps are ready for operation.
3. Turbine gland area is clean and loose debrises are removed.
4. One gland seal steam exhauster is kept in service.
5. One CEP is kept in service and condensate flow is established through GSC minimum recirculation.
6. Gland steam pressure control valve and Leak off control valves operation checking is complete. Oil level is OK in hydraulic actuators.
7. Charging of cooling water to condenser water boxes.
8. Control oil is charged.
Monday, September 15, 2025
ST-1 Shutdown
ST-1 SHUTDOWN PROCEDURE
(Note-Tie CB means CB for tie between station buses as applicable)
1. Switch OFF SD bus I/C DC supply .
2. Ensure SB/SD/UB-3B tie already closed at SB end.
3. Tie CB to SB/UB-3B CB at SD end, take its selection in manual in CR-1 to check healthiness of “CB in manual “contact by EMD.
4. Remove tripping of SB end tie CB with help of EMD (otherwise on closing SD end breaker, SB end tie CB will open & fault appear in it in CR-1 . To avoid it, EMD will remove this tripping of SB end tie CB) 5. Close tie CB at SD end . Ensure SB end tie CB will not trip.
6. Open SB bus I/C from ST-1 .
station Source c/o Procedure stage 1 Dadri
In stage 1 we have two station transformers
(ST1 and ST2). In case of planned outage or emergency tripping of one station
transformer the station bus of that station transformers can be charged via
available station transformer
Case 1 : Charging of station bus SC bus via station bus SA
- Open Station transformer 1 & 2 scheme in station common OWS (fig (i))
- See which breaker among CBE 213 and CBE 217 is in closed condition. In normal condition one breaker (CBE 213 or CBE 217) must be in closed condition.
- If CBE 213 is in closed condition then
a) Select Breaker CBE 216 ( SC incomer from ST#2) in SA-SC trip selector. (fig (i))
b) Turn the common synchronizer switch on common electrical vertical panel to check mode (fig (ii))
c) Put Synchroscope (on common electrical vertical panel ) in ON mode (fig (iii))
d) Select breaker CBE 217 (SC tie from SA) and check its permissive
e) After ensuring all the permissive are coming , close breaker CBE 217
f) After closing of CBE 217(SC tie from SA) breaker CBE 216 ( SC incomer from ST#2) will open in auto and SC bus will get charged by SA bus
Sunday, September 14, 2025
Saturday, September 13, 2025
Dadri stage 1 Light Up/Turbine rolling checklist/Steps
Unit start up Checklist | ||
| 1 | IOM sent to CISF | |
| 2 | Two ECW Pumps i/s | |
| 3 | Written clearance from: PP,RM.C&I,TM,AHM,EM | |
| 4 | Check Air, FG Pass dampers | |
| 5 | 2 Pass of ESP opened, All ACP i/s, Fields ready to be taken into service | |
| 6 | BT 50% | |
| 7 | IA, SA PR Adequate | |
| 8 | Aux PRDS charged from station | |
| 9 | LDO stations and AB, CD guns Normalised | |
| 10 | APH Soot blowing started with SB 26 | |
| 11 | Mills ABCD normal | |
| 12 | MS 1,2 Supply Normalised | |
| 13 | FA, BA evacuation system ready, AHP Clearance | |
| 14 | SH drains Manual Opened | |
| 15 | SH Manual vents, SH start up vents & drum vents Open | |
| 16 | MS lines drains u/s of HPBP @8.5m open | |
| 17 | Open Eco R/c E20 | |
| 18 | open CBD manual valves | |
| 19 | MS 203,204, HRH 203,204 CRH 203,204 open with manuals | |
| 20 | MS, HRH strainer drain to IBD MS 103/104, HRH 103,104 open | |
| 21 | MS, BD,SS,FW,HRH sampling line OK | |
| 22 | start CEP | |
| 23 | start BFP in r/c, wait for Chemistry clearance | |
| 24 | Take FRS 30%line and fill drum upto +50 mm | |
| 25 | Start APH, Scanner fan, ID fan, Fd fan put draft in auto, purge boiler | |
| 26 | Pull Vacuum | |
| 27 | Take AB13or AB24 and light up the Boiler | |
| 28 | After 30 minutes, Take other pair of AB | |
| 29 | Charge MOT cooler, LOTCV in auto with 45 Deg SP | |
| 30 | Check for TG Lub Oil filter | |
| 31 | Turbine SVs gagged removed | |
| 32 | Governing rack Normal, EHC Normal | |
| 33 | EHTC mimic: Speed SP<Turning speed,EHTC o/p:10%, Load controller ON | |
| 34 | All MAL dranis And MS/CRH/HRH drains to HPFT open | |
| 35 | Close Drum vents, SH Vents@2ksc | |
| 36 | CBD open | |
| 37 | Charge MS line @ 8ksc Drum Pr | |
| 38 | Charge HP, LP Bypass @ 10 lsc, close MS line drains u/s of HPBP | |
| 39 | close start up vents after HPLP Bypas charging | |
| 40 | EHTC mimic: Load ref 20MW,PRmax 50 MW | |
| 41 | Check X1, X2, X3 Before ESV opening | |
| 42 | Reset turbine by lower SD to 0%, Reset GRP | |
| 43 | Rolling: TG>>turbine all SGC>>turbine Seq>>Program ON>>startup | |
| 44 | Advance upto 101 to 105 for SD to reach 42% i.e. ESV opening | |
| 44 | For 540 rpm, check X4, X5, the advance upto 112 step, Then wait | |
| 45 | start PA Fans, Charge SW, SO, H2 Gas Cooler @ 540 rpm | |
| 46 | check Barring gear close@240rpm, JOP @ 540 rpm | |
| 47 | Inform S/Y to close Isolator | |
| 48 | For 3000 rp, X6 fulfills. | |
| 49 | From Program , advance upto 116 step, Program OFF | |
| 50 | DAVR: DAVR Reset, Close FCB, Excitation ON, make 16KV Gn TV | |
| 51 | Then Sel GCB form OWS, and selction: ATRS from ECP, EHTC: Synchroniser ON | |
| 52 | Open Speed Ref Pop-up for loading , As Unit sync, Load Turbine, Prmax:225 MW | |
| 53 | close HP Bypass , the LP Bypass to avoid HP/IP Trim | |
| 54 | check for GT Fans | |
| 55 | take Mill A | |
| 56 | close MS 101,102,103,104, HRH 1010,102,103,104 | |
| 57 | Put SLC Drains ON | |
| 58 | @20% Load : Charge D/A, LPHs | |
| 59 | @40% load: charge HPHs, Change over ST to UT | |
| 60 | Take Mills B, C@ 30% and 40% load | |
| 61 | Changeover FRS 30% to 100% @ 40% Load | |
| 62 | Take Additional mill D, and withdraw oil support | |
| 63 | Put Machine in CMC | |
| 64 | Close E20 v/v | |
| 64 | charge ESP Fields, and Normalise all Passes | |
Dadri stage 1 Important Drives Rating/Protections
MILL | 1 | SA Hdr PR <127mmWC for TD 1 Sec |
| 2 | PA Hdr<500, FEDCBA trip with TD 15 sec | |
| 3 | Feeder capacity 49 tph | |
| 4 | Full Load current: 54.7 A | |
| 5 | O/L Current: 65.25 A with TD 6 Sec | |
PA Fan | 1 | LO Pr 0.4 ksc: 0.9 ksc(standby starts) |
| 2 | HC Oil Pr: 0.8 ksc; 0.6 ksc(standby starts) | |
| 3 | Brg Temp: 90 Deg | |
| 4 | HC/ Return Oil Temp: 110/120 | |
| 5 | Vibration: 9mm/sec | |
| 6 | F/L Current/ O/L Current: 113.5/130.5 A | |
FD Fan | 1 | LO Pr 0.5 ksc: 0.9 ksc(standby starts) |
| 2 | Brg Temp: 100 Deg | |
| 3 | Vibration: 9mm/sec | |
| 4 | F/ L Current/ OL Current: 108/116.5 A | |
| 5 | Control Oil Pr: 8 ksc (standby starts) | |
ID Fan | 1 | LO Pr 0.7 ksc: 0.9 ksc(standby starts) |
| 2 | Brg Temp: 90 Deg | |
| 3 | Vibration: 9mm/sec | |
| 4 | F/L Current: 157.8 A | |
| 5 | O/L Current: 191.88 A | |
Misc Prot | 1 | Furnace: +150/-180 |
| 2 | Drum: +225(TD 10 sec)/-225(TD 5sec) | |
| 3 | Vacuum : -0.7 ksc/515 mmHG | |
| 4 | Vac p/p: Autostart -0.85 ksc/630 mmHG | |
| 5 | LO Pr:1.88 ksc | |
| 6 | Fire Protetion.1/2: -50, -100 | |
BFP | 1 | LO Pr: 0.5ksc/0.8ksc(AOP starts) |
| 2 | D/A Level: <700 mm | |
| 3 | Brg & HC Temp: 95 Deg | |
| 4 | WO Temp: 130 Deg | |
| 5 | Suction Pr: <1.7 ksc | |
| 6 | Full Load Current: 356.5 A | |
| 7 | O/L current: 399.28 A |
Dadri stage 1 High energy drains
| DADRI - COAL | ||
| High Energy Drain Valve Passing | ||
| [ STAGE - I ] | ||
| Date | 31.08.2025 | |
| S. No | Details of Passing Valve & Tag No | Unit-1 |
| 1 | MAL-11(UPSTREAM OF HP TURBINE CONTROL VALVE) | |
| 2 | Mal-26(UPSTREAM OF IP TURBINE CONTROL VALVE) | |
| 3 | MAL-15(DN STREAM OF HP TURBINE CONTROL VALVE) | |
| 4 | MAL-16(DN STREAM OF HP TURBINE CONTROL VALVE) | |
| 5 | MAL-22(HP TURBINE CASING DRAIN VALVE) | |
| 6 | MAL-31(DN STREAM OFIP TURBINE CONTROL VALVE) | |
| 7 | MAL-32(DN STREAM OF IP TURBINE CONTROL VALVE) | |
| 8 | MAL-65(CRH NRV UP STREAM) | |
| 9 | MAL-66(CRH NRV UP STREAM) | |
| 10 | MAL-12(UPSTREAM OF HP TURBINE CONTROL VALVE) | |
| 11 | MAL-27(UPSTREAM OF IP TURBINE CONTROL VALVE) | |
| 12 | MAL-47(HPH-5 EXTRACTION NRV UP STREAM) | |
| 13 | MAL-51(DA EXTRACTION NRV UP STREAM) | |
| 14 | MAL-54(LPH-3 EXTRACTION NRV UP STREAM) | |
| 15 | MAL-81(DRAIN FROM GLAND SEAL STEAM HEATER) | |
| 16 | MAL-55(LPH-2 EXTRACTION NRV UP STREAM) | |
| 17 | HRH-101(HRH LINE STRAINER DRAIN HP DRAIN FLASH BOX) | |
| 18 | HRH-102(HRH LINE STRAINER DRAIN TO HP DRAIN FLASH BOX) | |
| 19 | HRH-103(HRH LINE STRAINER DRAIN TO IBD TANK) | |
| 20 | HRH-104(HRH LINE STRAINER DRAIN TO IBD TANK) | |
| 21 | HRH-105 (LP BYPASS WARM UP LINE) | |
| 22 | HRH-106(LP BYPASS WARM UP LINE) | |
| 23 | MS-101(MS LINE STRAINER DRAIN HP DRAIN FLASH BOX) | |
| 24 | MS-102(MS LINE STRAINER DRAIN HP DRAIN FLASH BOX) | |
| 25 | MS-103(MS LINE STRAINER DRAIN TO IBD TANK) | |
| 26 | MS-104(MS LINE STRAINER DRAIN TO IBD TANK) | |
| 27 | CRH-101 (CRH LINE NRV DRAIN) | |
| 28 | CRH-102 (CRH LINE NRV DRAIN) | |
| 29 | BFP-1A | |
| 30 | BFP-1B | |
| 31 | BFP-1C | |
-
HP & LP Bypass Operation and Protection Purpose Boiler operation independent of the turbine Minimum steam flow through SH &...
-
Generator Air Tightness Test Period Of Test= 24 Hrs without a Break Air Pressure Drop (Allowed in 24 Hrs) : <=0.15 ksc Air Test Pre...



