Purpose
  • Boiler operation independent of the turbine
  • Minimum steam flow through SH & RH tubes during start-ups, low load operation & sudden unloading of unit
  • Utilized or building up of steam parameters
  • Avoiding the boiler trip on Reheat protection
  • No steam flow through Boiler steam tubes will lead to starvation & thereby overheating and lead to premature failure of tubes 
  • The capacity of HPLP bypass is 60% of full load turbine steam flow 
Reheat Protection:

RH protection (delay=10 sec) will act if
  1. TURBINE HP V/V & HPBP CLOSED [ either turbine HP stop v/v or HP CV in both HP line closed ] & [ both HP BP <2%]             OR
  2. TURBINE IP V/V & LP BP closed [ Either IP stop v/v or IP CV v/v in both IP line closed ] & [ Either LP BP stop v/v or LP BP C/V in both LP line is closed] OR  
  3. Generator ckt bkr open & [both HP BP closed OR both LP BP closed
HPBP Oil Supply Unit Interlocks:
  • Pump Auto off Oil Press high >160ksc
  • Pump Auto on Oil Press Low <120ksc
  • Pump Auto off Oil Temp high >70 DegC
  • Pump Auto off Oil Level low <18 Lit
  • Alarm Oil Press too high >170ksc
  • Alarm Oil Press too Low <90ksc
Pressure Mode:
Stg-2 Mode of Operation 
  • Initial Pressure Mode  -
    Importance to the load 
  • Fixed Pressure Mode -
    Importance to the Health of turbine.
HP BP Protection:
BP Valve Priority Close Conditions:
  • Condenser Vacuum Low (<-0.6 ksc)
  • Bypass Downstream Temp very high (>380 degC) 
                    Under these conditions 
  • Steam Press Controller Switches to Manual from Auto 
  • spray water valve will close
  • This protection will override the Fast opening signal & open push button operation
HP Bypass Fast Opening Conditions 
  • Generator Circuit Breaker Opening & Boiler on & no priority close
  • Turbine Trip & Boiler on & no priority close
  • Turbine Load Shedding Relay Operation
  • HP BP Pressure Controller Deviation > 8 ksc
  • Pressing the Fast Opening Button
BP Valve Auto Blocking Conditions  
  • Bypass valve priority close command
  • BP position transmitter failed 
  • OSU-1 &  2 Oil Pressure <90 ksc
  • Main steam Pressure transmitter failed
HP BP Interlocks:
BPE Valve Conditions  
  • Steam Bypass Valves BP1 or BP2<2 % Auto Close Command to ensure positive shut off
  • Steam Bypass Valves BP1 or BP2<2 % Spray Water Pressure Control Valve (BD Valve) close
  • Steam Bypass Valves BP1 or BP2>2 % Spray Water System (BPE1, BPE2, BD Valve) will switch over to Auto
BPE Valve Auto Blocking Conditions  
  • Bypass Downstream Temp very high (>380 degC)
  • BP auto command blocking
  • BPE valve position transmitter failed 
  • BPE Temp transmitter deviation high 
  • Therefore, it is necessary to make proper set values for Spray Water Header Pressure & HP BP downstream temperature before operating the Steam Bypass Valves
LP Bypass:
Functions of LP Bypass System are:
  • Maintaining minimum Steam Flow through Re-heater
  • Maintaining desired Steam Pressure in the Re-heater
  • Providing an alternative path for dumping the steam (not accepted by the IP & LP Turbines) into the condenser
LP BP System comprises of : 
  • Steam Pressure Control Loop
  • Valve Position Control Loop
  • Automatic Control Interface (ACI)
  • Condenser Temperature Protection
  • Tracking Unit
LPBP Protections:
Close LP Bypass under following conditions:





  1. Condenser Vacuum Low (<-0.6 ksc)
  2. Spray Water Pressure Low (<8 ksc)
  3. Condenser Wall Temperature High ( > 90 DegC)
  4. LPBP Down Steam Pressure High (>19 ksc)
  5. Spray Water valve open command at Steam pressure before bypass valve >6.8 ksc 