- Reduce Load to 300MW
- Slowly close flue gas outlet damper (2 in no. )for APH which has to be stopped
- Adjust other PAPH/SAPH flue gas outlet damper
- Close flue gas inlet damper
- Close SCAPH inlet , outlet & bypass damper. During Closing , Observe Air Flow.
- Close SAPH air outlet damper (2 in no.)
- Stop the SAPH motor once flue gas inlet temperature reduced below 150deg C
- Close Air motor main isolating valve & bypass isolating valve
Thermal Power Plant Operation Information guide. Please find here the Stand ard Operating Procedures, Instructions to operate various capacity Thermal power plants in India. This is as per my experience and any abnormality found please refer other sources. Thank you.
Wednesday, January 1, 2020
Stopping one SAPH
LIGHT UP CHECK POINTS
BEFORE
LIGHT UP ACTIVITIES
BOILER
SIDE
- MAN ,MATERIAL REMOVED AND BOILER IS READY FOR LIGHT UP.
Water-chemistry: 500 MW
Recommended Parameter Values
1. Boiler Water – pH = 9.1-9.4
2. Boiler Water – Specific Conductivity < 20.0 μs/cm
3. Boiler Water – Silica < 100 ppb
4. Boiler Water - Phosphate = 1-2 ppm
5. Boiler Water - Chloride < 0.5 ppm
1. Boiler Water – pH = 9.1-9.4
2. Boiler Water – Specific Conductivity < 20.0 μs/cm
3. Boiler Water – Silica < 100 ppb
4. Boiler Water - Phosphate = 1-2 ppm
5. Boiler Water - Chloride < 0.5 ppm
Switchyard Breaker arrangement: Rihand
Stage-I
GT#1
à 1-52
Main (GCB to Bus Bar-1) à 2-52 (Tie-GCB to bus Bar-2) à 3-52(IBT-1
i/c)
GT#2 à 7-52Main (GCB to Bus Bar-2) à 8-52((Tie-GCB
to bus Bar-1)
Bus bar-1 à 4-52
(H1) à 5-52(Tie H1-S2) à 6-52(S2)
à Bus Bar-2
Bus bar-2 à 10-52
(S1) à 11-52(Tie S1-H2) à 12-52(H2)
à Bus Bar-1
Bus-1 ß13-52(Bus-coupler-1) à
Bus-3
Bus-2 ß14-52(Bus-coupler-2) à
Bus-4
Turbine Governing system
Key Points
Ø Governing-
Regulation of Turbine Speed under No Load and Varying Load
Ø Others
Works: CV Actuation/ Initial Run-up & Synchronization/ Load Variation to
meet Grid Freq
Ø 500 MW
KWU: Throttle Governed Machine
Ø 2
Governors , EHC and HG connected in Parallel: Only One at a time through Hyd
Minimum slection
Ø CVs
Open according to Secondary oil Pressure
Ø Between
100 MW to 525 MW , Load variation done
by HPCV throttling
Important Procedures
Vacuum Pulling : Procedure:
Ø Close
RH Vents, CRH, HRH UFT drains
Ø Close
Vacuum Breaker
Ø Open
8.5 m steam Manual valve full Both (100%), Temp> 250 Deg ( Open
Ø Start
GSC Exhauster Fan
Ø Start
Both Vacuum pumps ( Casing Empty, Receiver tank Level adeq)
Ø At
-0.2 ksc charge steam gradually ( lower Controller from 50% à 0 %)
Ø Build
Vacuum upto -0.9 ksc
Hydrogen Purging
Ø SLC AS
SOP Off, SLC DC SOP Off, SLC H2 SOP Off
Ø Suppy
of DC SOP Off
Ø Start
one AC SOP ( DP=1.5 ksc)
Ø Dew
Point Air=<-10 Deg, clearance from Chemist
Ø H2
(Isolated Position), CO2(Isolated Position), Air Inlet(Open), Casing vent (
Closed)
Ø Fill
and Pressurise upto 0.5 ksc
Cold start-up
Points to Remember
Ø maximum
of HP casing and HP shaft is less than 150°C(more
than 5 days)
Ø It
requires soaking of Turbine at 360 rpm with steam(40ksc,360 Deg)
Ø An
upper limit of 200°
C/hr. saturation temp gradients can be allowed, i.e.
approximately the boiler pressure can be brought to 20 Kg/ Cm2 within
an hour of cold start up
Ø But
actual temp gradient is limited by the thick walled Y piece
provided in the main steam and HRH lines
Ø maximum
differential temp allowed between inner (98%) and mid wall temp (50%)
is ±40°C
Ø Start
only two CC pumps in order to minimize flashing in down
comers (and subsequent vibration) when the boiler water is in the
range of 85°
to 125°
C
IBT Outage
Consequences on Stage-2 ( Station
Transformer Tripped)
Ø 132
KV Switchyard dead results in tripping of -Station Transformers, Construction
Transformer, Misc Transformer
Ø All
colony power( Lighting,Water supply) will get interrupted
Ø Power
Supply to DM Plant, HFO Pump house, PTCW Pump house, Offsite Board, ADPH,
Ø Following
Board will get dead:
§ OBA,OBB,OBC,OBD
(11 KV station Board)
§ OCA,OCB
(3.3 KV Station aux Board), ADPH MCC, CHP Transformers
§ DMPT,
CWST, WTPT,BTST,ODA,ODB(Station Service), ODC(FW Pump House),ODD ( Offsite ):
3.3 KV
§ OQA,OQB(St.
Serv),3SA,4SA(Air Washer MCC),3TA,4TA(Unit Ventilation MCC),OTA(HVAC ) : 415 V
§ OSA(SW
MCC), OTB(Serv Bldg Ventilation MCC), FOPH : 415 V
Instrument Air supply Failure
Reasons of Failure:
Ø Failure
of control supply of compressor
Ø Loss
of Cooling Water (SG ECW Pump Trip)
Ø Massive
leakage in IA supply Header
Ø One
Unit Under Overhaul. Unit Aux Board/ Station Aux board got Tripped of that Unit
Ø Total
Black Out of any stage
DG Load Trial and Regular checks
Requirements:
1
|
Inform & Ensure
availability of TMD/EMD/C&I
|
|
2
|
SG/TG/BOP source-2 AC
Power Supply Interruption. Inform C&I for Standby chargers
|
|
3
|
Ensure DG Set Tank Oil
Level Adequate
|
|
4
|
Evacuate and Isolate
Boiler Passenger, Service Building Lift and Isolate. Inform EMD(temporary
supply )
|
|
5
|
Arrange 3 Walky Talky
: 1-CR 2-DG board 3-DG Set room
|
|
6
|
Note Down Initial
Parameters of DG Set |
Furnace Air Tightness Test
Ø Scope-
Boiler Furnace, Air and FG Duct upto ID Fan Inlet
Ø Why-
To test Tightness of Furnace wrt Environment not for Strength
Ø Ensure-
All PTWs of BMD( PP, Rotary, Mills, Ash handling) cancelled and Clearance
Available
Emergency Instructions:220 V DC Failure
220 V DC Failure
Unit condition
Ø DCDB
section-1 & 2 under voltage alarm in LVS-5
Ø All
HT/LT Breakers Indication Becomes Bad
Ø Boiler
will Trip on MFT ( after 2 Sec)
Ø Turbine
will Trip on MFT
Ø Generator
will not Trip as GCB Protection will not
act
Ø Generator
will run as Synchronous Motor
Start-Up After 8 Hours of Shutdown ( Hot start-UP)
Unit condition
1
|
At least 2 BCW pump in Serrvice
|
||
2
|
Both SAPH and PAPH Running
|
||
3
|
Turbine : On Barring
(AOP,JOP,SOP, HPCF in service)
|
||
4
|
Generator: PW system, Seal Oil
system, Gas system
|
||
5
|
Condenser Pass : Both Charged
|
||
6
|
PAC & IAC : 1 PAC & 2
IAC in Service
|
||
7
|
CEP & Make-up : 1 CEP with H/W Make-up on auto |
Saturday, December 28, 2019
Monday, December 23, 2019
Thursday, December 19, 2019
Saturday, December 14, 2019
Friday, December 13, 2019
Wednesday, December 11, 2019
Turbine and TDBFP Overspeed & Oil Injection Test Procedure
Oil Injection of Main Turbine:
- Press Test Valve
- Turn Test Hand-wheel Anticlockwise slowly ( to develop Test Oil)
- Note Turbine Speed, Test Oil Pressure, Primary Oil Pressure when Bolts Operate(Aux Trip Oil becomes 0)
- Turn Test Hand-wheel Clockwise slowly (Test Oil pressure becomes 0)
Monday, December 9, 2019
Sunday, December 8, 2019
Sunday, November 17, 2019
Saturday, November 16, 2019
Friday, November 15, 2019
Thursday, November 14, 2019
Wednesday, December 19, 2018
Tuesday, December 18, 2018
Monday, December 17, 2018
Friday, December 14, 2018
Thursday, December 13, 2018
Volumetric Vs Gravimetric Mode : Feeder
Volumetrric Vs Gravimetric Mode : Feeder
- Coal properties constantly vary due to sizing differences and the adverse impact of moisture. These affect heating value, flow characteristics and density.The resultant density changes are measured by the Gravimetric Feeder.
- The gravimetric feeder compensates for the variation in bulk density and feeds a fixed weight of coal in response to a boiler fuel demand
- This ability to accurately weigh the coal provides significant improvement over volumetric types in terms of matching the fuel delivered by the feeder to the actual process energy required on coal fired units.
Benefits of Gravimetric Feeder
- Fuel Savings through Improved Boiler Efficiency
- Improved Combustion Efficiency/LOI
- Less Slagging and Fouling, leading to Less Corrosion
- Less NOx through Better Control of Excess Air
- Stability and Improved Response of Combustion Controls
- Improved Pulverizer/Cyclone/Combustor Performance
- Reduced Safety Concerns
How It Works : Gravimetric Mode
- Gravimetric feeder weighs material on a belt between two fixed points (span) precisely located in the feeder body.
- A roller, located midway in the span and supported at each end by precision load cells, supports half the weight on the span
- The load cells generate an electrical signal directly proportional to the weight supported.
- The microprocessor takes samples of the output of each load cell many times a second.
- If the load cell outputs are within the expected range, they are added to obtain total weight per unit of belt length.
- Belt speed is determined by sampling the output of a tachometer attached to the motor shaft, multiplied by a calibration factor to convert it into a belt speed signal
- The microprocessor multiplies the speed and weight signal for the feeder rate of fuel output.
- Finally, the microprocessor matches the feeder output to the output required by the boiler control, by adjusting the feeder motor speed.
- Feeders provide an accuracy of +/- ½ of one percent of totalized weight when calibrated and maintained
Volumetric feeding
Volumetric feeder is Open-loop device
- Volumetric mode is set-speed constant , choke-fed or flooded infeed of a particulate solid and it feeds by volume only.
- Feed must have consistent bulk density
- As there is no information on feedback of feeder ouput and drive control system
Wednesday, December 12, 2018
Monday, December 10, 2018
Subscribe to:
Comments (Atom)
-
HP & LP Bypass Operation and Protection Purpose Boiler operation independent of the turbine Minimum steam flow through SH &...
-
Generator Air Tightness Test Period Of Test= 24 Hrs without a Break Air Pressure Drop (Allowed in 24 Hrs) : <=0.15 ksc Air Test Pre...








