Emergency Instructions:220 V DC Failure
220 V DC Failure
Unit condition
Ø DCDB
section-1 & 2 under voltage alarm in LVS-5
Ø All
HT/LT Breakers Indication Becomes Bad
Ø Boiler
will Trip on MFT ( after 2 Sec)
Ø Turbine
will Trip on MFT
Ø Generator
will not Trip as GCB Protection will not
act
Ø HP/IP/LP
Casing Exhaust Temperature will start increasing
Ø 400
KV Breakers can be Operable
Ø Feeders
of Mill will Trip on MFT
Ø Fans(ID,
FD, PA), Mills, BCW Pumps etc will continue to run
Ø DC
Drives can not come in service
Actions
Ø Sequence
to Trip Drives:
·
PA fan
·
Mills
·
One set ID/FD
·
Another set of ID/FD
·
BCW Pumps
·
MDFP
·
CEP
·
SG ECW
·
TG ECW
·
Air compressors
·
CW Pumps
Ø Start
DG set
Ø Start
AOP-1, SOP-1, AOP-1 of TDBFPs, PW-1
Ø Trip
Normal Incomer breaker from unit service
Board to Emergency board from Switchgear
Ø Close
DG set incomer breaker to emergency Board from Switchgear
Ø Start
AOP-2, SOP-2, AOP-2 of TDBFPs, PW-2
Ø Trip
400 KV Main/Tie GCB from CCR/Switchyard
Ø Trip
Station Transformer after shifting critical equipments
Ø This
will result in Total Power Failure with Emergency Board in charged condition