FUNCTIONS OF FSSS

FUNCTIONS OF FSSS

  • Prevent any fuel firing unless a satisfactory furnace purge sequence has first been completed.
  • Prevent start-up of individual fuel firing equipment unless certain permissive, interlocks have been satisfied.
  • Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment.
  • Subject continued operation of fuel firing equipment to certain safety interlocks remaining satisfied.
  • Provide component status feedback to the operator and, in some cases, to the unit control system  and / or to the data logger.
  • Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.
  • Effect a Master Fuel Trip upon certain adverse Unit operating condition
INTERLOCKS COVERED UNDER FSSS


  • PURGE PERMISSIVES   
    • 1. POST TRIP PURGE CYCLE
    • 2. FURNACE PURGE CYCLE
  • HOTV OPEN/CLOSE INTERLOCKS
  • HORV OPEN/CLOSE INTERLOCKS
  • OIL GUNS START/STOP CYCLE
  • BOILER PROTECTION LOGICS
  • PA FAN INTERLOCKS COVERED UNDER FSSS
  • COAL MILL START/STOP INTERLOCKS
  • COAL FEEDER START/STOP INTERLOCKS
  • SCANNER AIR FANS
  • SEAL AIR FANS
  • DAMPER INTERLOCKS

POST-FIRING PURGE PURGE PERMISSIVE

  •  All HFO Nozzle Valves Closed
  •  HFO Trip Valve closed
  •  All Pulverizers Off.
  •  All Feeders Off
  •  All Flame Scanners Sense No Flame
  •  Air Flow > 30 %
  •  Mode Permit Proven (Air Flow < 40 % And Nozzle Tilt Horizontal)

PRE-FIRING PURGE PURGE PERMISSIVE

  •  All HFO Nozzle Valves Closed
  •  HFO Trip Valve closed
  •  No Boiler Trip From MFR A & B
  •  All Pulverizers Off.
  •  All Feeders Off
  •  All Flame Scanners Sense No Flame
  •  All Auxiliary Air Dampers Modulating and furnace to wind box P OK
  •  Both PA fans Off
  •  All HAGS Closed
  •  Air Flow > 30 %
  • Mode Permit Proven (Air Flow < 40% And Nozzle tilt Horizontal)
  • Drum Level Satisfactory
  • FSSS AC / DC Power Available.



HOTV INTERLOCKS
TO OPEN HOTV :
Permissives : 
SET I 
  • No. Boiler Trip persisting
  • HFO Header temperature  satisfactory >950 C
  • HFO supply press sat. > 15 Kg / cm2
  • All HONV’s closed
  • No close / Trip command
  • Open PB depressed 

OR
SET II 

  • All HONV’s closed
  • MFT acted
  • HORV open
  • Open PB depressed

HOTV INTERLOCKS

1. HOTV CLOSES AUTOMATICALLY UNDER FOLLOWING CONDITIONS : 
Any HONV not closed  AND
a) HFO pressure low < 3 Kg/cm2 
OR
b) Atom. steam Pr. low < 3.5 Kg/cm2 
OR 
c) HFO Header Temperature Lo-Lo for > 2  secs.  < 95 0 C
2. Any HONV not closed and MFT acted
3. Loss of critical power > 2 Secs
4. HOTV can be closed manually by pressing the close push button.




HORV INTERLOCKS

  •  HORV can be opened by pressing the OPEN Push button (PB)  from Console if All the HONV s are  closed.
  •  HORV closes automatically when any HONV is not closed OR  by  pressing close PB.




PAIR FIRING MODE (START UP)

  • Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)
  • When pair 1-3 start push button is pressed the following events take place
  • A  30 second counting period is started
  • A  70 second counting period is started
  • Oil Gun No-1 advances from retracted position if
  • It is engaged, corresponding scavenge valve is closed, atomising steam and HFO isolation valves are open.
  • HEA ignitor advances.
  • Atomising steam valve opens.
  • Ignitor starts sparking.
  • HFO Nozzle valve for corner 1 opens
  • HFO catches fire and flame indication comes.
  • After 25 seconds ignitor retracts.
  • When the 30 second counting period expires command will 
  • go to corner 3 and same events will take place.
  • Corner 2-4 can also be placed exactly in the same manner.
ELEVATION FIRING MODE (START UP)
  • Elevation firing mode is selected when any feeder is proven.
  • Oil elevation is placed in service when Pair 1-3 or Pair   2-4 start Push Button is pressed. In elevation firing mode also the oil guns are proven on pair basis.
  • First command goes for placing Pair 1-3 into service and Pair 1-3 is placed into service exactly in the same way as in the pair mode.
  • First start command goes to corner-1 then after 30 second start command goes to corner-3.
  • After the start command has gone to corner 3, a 30 second counting period is started. When 30 seconds counting period expires then start command goes for corner 2-4 and corner   2-4 are placed into service exactly in the same manner as in the pair mode.
PAIR FIRING MODE (SHUT DOWN)

  • Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)
  • When pair 1-3 stop push button is pressed the following events take place
  • A  30 second counting period is started
  • A  340 second counting period is started
  • Oil Gun No-1 HFO nozzle valve closes.
  • Scavenge and atomising steam valve opens.
  • HEA ignitor advances and spark remains for 15 seconds.
  • When atomising steam valve is proven fully open, a 5 minutes counting period starts.
  • When 5 minutes counting period expires scavenge valve and atomising steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed.
  • Oil Gun corner no-1 retracts to its home position.
  • When the 30 second counting period expires stop command will go to corner 3 and same events will take place.
  • Corner 2-4 can  be shut-down exactly in the same manner.
ELEVATION FIRING MODE (SHUTDOWN)
  • Elevation firing mode is selected when any feeder is proven.
  • By pressing stop push-button of  Pair 1-3 or Pair 2-4 the following events will take place.
  • Corner 1-3 will be shut-down in the similar way as in the pair mode.
  • When stop command has gone to corner 3, a 30 second counting period is started.
  • When 30 seconds counting period expires then stop command goes for corner 2-4 and corner 2-4 are shut-down exactly in the same manner as in the pair mod
BOILER TRIP CONDITIONS
  • Both FD Fans Off
  • All ID Fans Off
  • Inadequate Waterwall Circulation
  • Loss  Of Reheat Protection
  • Deaerator level Lo-Lo  ( -2134 mm 2 / 3 logic)
  • All Boiler Feed Pumps Off
  • Drum Level High-High (> + 250 mm, delay of 10 seconds)
  • Drum Level Lo-Lo (< - 375 mm, delay 10 seconds)
  • Elevation Power Failure For > 2 seconds.
  • Furnace Pressure High-High  (> + 325 mmWC, 2 / 3 logic)
  • Furnace Pressure Lo-Lo  ( < -250 mmWC, 2 / 3 logic )
  • Loss Of  All Fuel
  • Unit Flame Failure
  • Loss Of Critical Power For > 2 seconds
  •  Loss Of  220 V DC For >  2 seconds
  • Loss Of ACS Power >  2 seconds
  • Simulator Trip
  • Air Flow < 30 %
  • Both Emergency Push Buttons Pressed. 
BOILER TRIP

  • When the boiler trips the following events takes place
  • Boiler trip red lamp comes on.
  • MFT A & B trip lamp comes on and reset lamp goes off.
  • Cause of trip memory can not be reset till the furnace purge is completed.
  • F D Fans Control is transferred to manual. 
  • I D fans vane position is transferred to manual.
  • Pulverizers are tripped.
  • Coal feeders are tripped.
  • P A  Fans are tripped.
  • Cold air dampers opens 100 %.
  • HFO trip valve closes.
  • All HFO Nozzle valves closes.
  • Upper and Lower Fuel air damper opens.
  • Auxiliary air damper opens and control is transferred to manual.
  • Loss of all fuel trip protection disarms.
  • S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless furnace purge is completed.
  • Turbine Trips
INADEQUATE WATER WALL CIRCULATION

  • BOILER LOAD < 60 % AND NO BCW PUMP ON OR PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI.
  • BOILER LOAD > 60 % AND LESS THAN TWO PUMPS  OR  PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI.





REHEAT PROTECTION

  • TURBINE TRIP OR GENERATOR CIRCUIT BREAKER OPEN AND HP/LP BYPASS OPENING < 2 %.
  • TURBINE WORKING (HP & IP CVS OPENING > 2 % AND LOAD SHEDDING RELAY OPERATED AND HP/LP BYPASS OPENING < 2 %.
  • TURBINE NOT WORKING AND BOILER WORKING AND  HP/LP BYPASS OPENING < 2 %

MILL INTERLOCKS   
START PERMISSIVES :

  • Mill starts after the ‘ON’ push button is pressed if following
  • conditions are fulfilled.
  • Pulveriser Ready available signal will be available if following conditions are fulfilled
  • M.D.V. is open (all four)
  • Mill outlet temp < 93 0 C
  • Feeder local switch in Remote
  • Pulv. start permit (if Nozzle tilt Horizontal  & air flow < 40 % )
OR 
( Any feeder  proven and NO MFT )
  • Cold air gate open
  • Tramp iron valve open
  • Feeder inlet gate open
  • Lub oil level & temp. adequate
  • Lub oil pressure not low for more than 300 sec
  • No Mill trip existing
  • P.A. permit available. 
    1. Hot P.A. duct Pressure. not low ( < 625 mm wc)
    2. P.A. duct pr. not lo-lo ( > 500 mmWc AND  
    3. Both FD s ON and both PA fans ‘ON’ or (Any PA fan ON and any FD Fan  ‘ON’ and > 4 mills not ON)   
  •  No Auto pulv unsuccessful start
  •  Seal air Header to mill under bowl DP satisfactory > 8" wc
  •  Mill not ‘ON’
  •  Pulv Ignition permit available.
 FOR Mill A
  •  AB elevation 3/4 HONV’s open
OR  
  •  Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)
For Mill B
  •  AB elevation proven 3/4 HONV’s open
OR
  •  Boiler load > 30 % and Feeder A or Feeder C proven.
For Mill C
  •  CD elevation proven  
         OR
  •  AB oil elevation and feeder B proven  
        OR
  •  Boiler load > 30 % & either feeder B or Feeder D proven
For Mill D
  •  CD elevation proven
OR
  • Boiler load > 30 % and either feeder C or feeder E proven.
  • For Mill E,F,G & H identical logic.

PULVERISER TRIP CONDITIONS

  • Auto / manual mode selected to manual & stop PB depressed.   
  • Pulv. start command given  & not ‘ON’ for > 2 Secs.
  • Loss of Elevevation OR Unit Power for > 2 Secs
  • Pulv ‘ON’ & seal air / under DP Low  > 1 min < 5”wc
  • Pulv  ‘ON’ and lub oil pump OFF > 10 sec.
  • Pulv ‘ON’ and lub oil pr. low > 10 secs. < 1.76 Kg/cm2
  • Ignition permit required (> 180 secs) & ignition permit lost (i.e. within 180 sec of feeder start)
  • Any of the MDV is  not fully open
  • Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)
  • Hot PA duct. pr. Lo - Lo  =  < 525mm WC (instantaneous)
  • MFT    
  • PA / FD Fan trip
    1. If both PA Fans & both FD fans running  & any PA or any FD Fan trips then mills start tripping from top elevations with 2 secs time delay till 4 mills are available.
    2. If both PA / FD fans trip then all mills will trip.

PULV. SEAL AIR VALVES INTERLOCKS

  •  Valve opens when Pulv. start command is given OR Mill is ON
  •  Valve closes when Pulv. is OFF
HOT AIR GATE INTERLOCKS
  •  Hot  air gate (HAG) opens when Pulv is ‘ON’ AND Hot air gate open P.B depressed  or auto HAG open command is  there  AND  NO HAG  close command.
  •  Hot air gate closes when
1. Loss of power > 2 secs
2. Pulv. off
3. Pulv. outlet temp > 93 0 C
4. Close P.B. depressed
5. Feeder Trips.(Delay 40 sec) 
6. Auto pulv. unsuccessful start 
7. Auto pulv. run feeder speed to minimum 

FEEDER START  PERMISSIVES

  •  Pulveriser Ready is available
  •  Feeder speed demand at minimum
  •  Pulveriser manual mode
  •  Pulveriser ignition permit available
  •  No feeder stop command
  •  No  MFT
  •  Pulveriser ‘ON’
FEEDER TRIP CONDITION
  •  Ignition energy removed within 180 secs of feeder start
  •  Feeder in manual mode & stop PB depressed 
  •  Auto Pulv. Feeder stop command
  •  Pulv. OFF 
  •  MFT
  •  No coal on belt Discharge plugged 