FUNCTIONS OF FSSS
- Prevent any fuel firing unless a satisfactory furnace purge sequence has first been completed.
- Prevent start-up of individual fuel firing equipment unless certain permissive, interlocks have been satisfied.
- Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment.
- Subject continued operation of fuel firing equipment to certain safety interlocks remaining satisfied.
- Provide component status feedback to the operator and, in some cases, to the unit control system and / or to the data logger.
- Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.
- Effect a Master Fuel Trip upon certain adverse Unit operating condition
INTERLOCKS COVERED UNDER FSSS
- PURGE PERMISSIVES
- 1. POST TRIP PURGE CYCLE
- 2. FURNACE PURGE CYCLE
- HOTV OPEN/CLOSE INTERLOCKS
- HORV OPEN/CLOSE INTERLOCKS
- OIL GUNS START/STOP CYCLE
- BOILER PROTECTION LOGICS
- PA FAN INTERLOCKS COVERED UNDER FSSS
- COAL MILL START/STOP INTERLOCKS
- COAL FEEDER START/STOP INTERLOCKS
- SCANNER AIR FANS
- SEAL AIR FANS
- DAMPER INTERLOCKS
POST-FIRING PURGE PURGE PERMISSIVE
- All HFO Nozzle Valves Closed
- HFO Trip Valve closed
- All Pulverizers Off.
- All Feeders Off
- All Flame Scanners Sense No Flame
- Air Flow > 30 %
- Mode Permit Proven (Air Flow < 40 % And Nozzle Tilt Horizontal)
PRE-FIRING PURGE PURGE PERMISSIVE
- All HFO Nozzle Valves Closed
- HFO Trip Valve closed
- No Boiler Trip From MFR A & B
- All Pulverizers Off.
- All Feeders Off
- All Flame Scanners Sense No Flame
- All Auxiliary Air Dampers Modulating and furnace to wind box P OK
- Both PA fans Off
- All HAGS Closed
- Air Flow > 30 %
- Mode Permit Proven (Air Flow < 40% And Nozzle tilt Horizontal)
- Drum Level Satisfactory
- FSSS AC / DC Power Available.
HOTV INTERLOCKS
TO OPEN HOTV :Permissives :
SET I
- No. Boiler Trip persisting
- HFO Header temperature satisfactory >950 C
- HFO supply press sat. > 15 Kg / cm2
- All HONV’s closed
- No close / Trip command
- Open PB depressed
OR
SET II
- All HONV’s closed
- MFT acted
- HORV open
- Open PB depressed
HOTV INTERLOCKS
1. HOTV CLOSES AUTOMATICALLY UNDER FOLLOWING CONDITIONS :
Any HONV not closed AND
a) HFO pressure low < 3 Kg/cm2
OR
b) Atom. steam Pr. low < 3.5 Kg/cm2
OR
c) HFO Header Temperature Lo-Lo for > 2 secs. < 95 0 C
2. Any HONV not closed and MFT acted
3. Loss of critical power > 2 Secs
4. HOTV can be closed manually by pressing the close push button.
HORV INTERLOCKS
- HORV can be opened by pressing the OPEN Push button (PB) from Console if All the HONV s are closed.
- HORV closes automatically when any HONV is not closed OR by pressing close PB.
PAIR FIRING MODE (START UP)
- Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)
- When pair 1-3 start push button is pressed the following events take place
- A 30 second counting period is started
- A 70 second counting period is started
- Oil Gun No-1 advances from retracted position if
- It is engaged, corresponding scavenge valve is closed, atomising steam and HFO isolation valves are open.
- HEA ignitor advances.
- Atomising steam valve opens.
- Ignitor starts sparking.
- HFO Nozzle valve for corner 1 opens
- HFO catches fire and flame indication comes.
- After 25 seconds ignitor retracts.
- When the 30 second counting period expires command will
- go to corner 3 and same events will take place.
- Corner 2-4 can also be placed exactly in the same manner.
ELEVATION FIRING MODE (START UP)
- Elevation firing mode is selected when any feeder is proven.
- Oil elevation is placed in service when Pair 1-3 or Pair 2-4 start Push Button is pressed. In elevation firing mode also the oil guns are proven on pair basis.
- First command goes for placing Pair 1-3 into service and Pair 1-3 is placed into service exactly in the same way as in the pair mode.
- First start command goes to corner-1 then after 30 second start command goes to corner-3.
- After the start command has gone to corner 3, a 30 second counting period is started. When 30 seconds counting period expires then start command goes for corner 2-4 and corner 2-4 are placed into service exactly in the same manner as in the pair mode.
PAIR FIRING MODE (SHUT DOWN)
- Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)
- When pair 1-3 stop push button is pressed the following events take place
- A 30 second counting period is started
- A 340 second counting period is started
- Oil Gun No-1 HFO nozzle valve closes.
- Scavenge and atomising steam valve opens.
- HEA ignitor advances and spark remains for 15 seconds.
- When atomising steam valve is proven fully open, a 5 minutes counting period starts.
- When 5 minutes counting period expires scavenge valve and atomising steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed.
- Oil Gun corner no-1 retracts to its home position.
- When the 30 second counting period expires stop command will go to corner 3 and same events will take place.
- Corner 2-4 can be shut-down exactly in the same manner.
ELEVATION FIRING MODE (SHUTDOWN)
- Elevation firing mode is selected when any feeder is proven.
- By pressing stop push-button of Pair 1-3 or Pair 2-4 the following events will take place.
- Corner 1-3 will be shut-down in the similar way as in the pair mode.
- When stop command has gone to corner 3, a 30 second counting period is started.
- When 30 seconds counting period expires then stop command goes for corner 2-4 and corner 2-4 are shut-down exactly in the same manner as in the pair mod
BOILER TRIP CONDITIONS
- Both FD Fans Off
- All ID Fans Off
- Inadequate Waterwall Circulation
- Loss Of Reheat Protection
- Deaerator level Lo-Lo ( -2134 mm 2 / 3 logic)
- All Boiler Feed Pumps Off
- Drum Level High-High (> + 250 mm, delay of 10 seconds)
- Drum Level Lo-Lo (< - 375 mm, delay 10 seconds)
- Elevation Power Failure For > 2 seconds.
- Furnace Pressure High-High (> + 325 mmWC, 2 / 3 logic)
- Furnace Pressure Lo-Lo ( < -250 mmWC, 2 / 3 logic )
- Loss Of All Fuel
- Unit Flame Failure
- Loss Of Critical Power For > 2 seconds
- Loss Of 220 V DC For > 2 seconds
- Loss Of ACS Power > 2 seconds
- Simulator Trip
- Air Flow < 30 %
- Both Emergency Push Buttons Pressed.
BOILER TRIP
- When the boiler trips the following events takes place
- Boiler trip red lamp comes on.
- MFT A & B trip lamp comes on and reset lamp goes off.
- Cause of trip memory can not be reset till the furnace purge is completed.
- F D Fans Control is transferred to manual.
- I D fans vane position is transferred to manual.
- Pulverizers are tripped.
- Coal feeders are tripped.
- P A Fans are tripped.
- Cold air dampers opens 100 %.
- HFO trip valve closes.
- All HFO Nozzle valves closes.
- Upper and Lower Fuel air damper opens.
- Auxiliary air damper opens and control is transferred to manual.
- Loss of all fuel trip protection disarms.
- S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless furnace purge is completed.
- Turbine Trips
INADEQUATE WATER WALL CIRCULATION
- BOILER LOAD < 60 % AND NO BCW PUMP ON OR PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI.
- BOILER LOAD > 60 % AND LESS THAN TWO PUMPS OR PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI.
REHEAT PROTECTION
- TURBINE TRIP OR GENERATOR CIRCUIT BREAKER OPEN AND HP/LP BYPASS OPENING < 2 %.
- TURBINE WORKING (HP & IP CVS OPENING > 2 % AND LOAD SHEDDING RELAY OPERATED AND HP/LP BYPASS OPENING < 2 %.
- TURBINE NOT WORKING AND BOILER WORKING AND HP/LP BYPASS OPENING < 2 %
MILL INTERLOCKS
START PERMISSIVES :
- Mill starts after the ‘ON’ push button is pressed if following
- conditions are fulfilled.
- Pulveriser Ready available signal will be available if following conditions are fulfilled
- M.D.V. is open (all four)
- Mill outlet temp < 93 0 C
- Feeder local switch in Remote
- Pulv. start permit (if Nozzle tilt Horizontal & air flow < 40 % )
OR
( Any feeder proven and NO MFT )
- Cold air gate open
- Tramp iron valve open
- Feeder inlet gate open
- Lub oil level & temp. adequate
- Lub oil pressure not low for more than 300 sec
- No Mill trip existing
- P.A. permit available.
- Hot P.A. duct Pressure. not low ( < 625 mm wc)
- P.A. duct pr. not lo-lo ( > 500 mmWc AND
- Both FD s ON and both PA fans ‘ON’ or (Any PA fan ON and any FD Fan ‘ON’ and > 4 mills not ON)
- No Auto pulv unsuccessful start
- Seal air Header to mill under bowl DP satisfactory > 8" wc
- Mill not ‘ON’
- Pulv Ignition permit available.
FOR Mill A
- AB elevation 3/4 HONV’s open
OR
- Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)
For Mill B
- AB elevation proven 3/4 HONV’s open
OR
- Boiler load > 30 % and Feeder A or Feeder C proven.
For Mill C
- CD elevation proven
OR
- AB oil elevation and feeder B proven
OR
- Boiler load > 30 % & either feeder B or Feeder D proven
For Mill D
- CD elevation proven
OR
- Boiler load > 30 % and either feeder C or feeder E proven.
- For Mill E,F,G & H identical logic.
PULVERISER TRIP CONDITIONS
- Auto / manual mode selected to manual & stop PB depressed.
- Pulv. start command given & not ‘ON’ for > 2 Secs.
- Loss of Elevevation OR Unit Power for > 2 Secs
- Pulv ‘ON’ & seal air / under DP Low > 1 min < 5”wc
- Pulv ‘ON’ and lub oil pump OFF > 10 sec.
- Pulv ‘ON’ and lub oil pr. low > 10 secs. < 1.76 Kg/cm2
- Ignition permit required (> 180 secs) & ignition permit lost (i.e. within 180 sec of feeder start)
- Any of the MDV is not fully open
- Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)
- Hot PA duct. pr. Lo - Lo = < 525mm WC (instantaneous)
- MFT
- PA / FD Fan trip
- If both PA Fans & both FD fans running & any PA or any FD Fan trips then mills start tripping from top elevations with 2 secs time delay till 4 mills are available.
- If both PA / FD fans trip then all mills will trip.
PULV. SEAL AIR VALVES INTERLOCKS
- Valve opens when Pulv. start command is given OR Mill is ON
- Valve closes when Pulv. is OFF
HOT AIR GATE INTERLOCKS
- Hot air gate (HAG) opens when Pulv is ‘ON’ AND Hot air gate open P.B depressed or auto HAG open command is there AND NO HAG close command.
- Hot air gate closes when
1. Loss of power > 2 secs
2. Pulv. off
3. Pulv. outlet temp > 93 0 C
4. Close P.B. depressed
5. Feeder Trips.(Delay 40 sec)
6. Auto pulv. unsuccessful start
7. Auto pulv. run feeder speed to minimum
FEEDER START PERMISSIVES
- Pulveriser Ready is available
- Feeder speed demand at minimum
- Pulveriser manual mode
- Pulveriser ignition permit available
- No feeder stop command
- No MFT
- Pulveriser ‘ON’
FEEDER TRIP CONDITION
- Ignition energy removed within 180 secs of feeder start
- Feeder in manual mode & stop PB depressed
- Auto Pulv. Feeder stop command
- Pulv. OFF
- MFT
- No coal on belt Discharge plugged