CEP Protection
CEP
START PERMISSIVE
1. CEP Suction
valve open AND
Hotwell
level not low (>-250 mm) 2/3 AND
Swgr. available AND
Swgr. not
disturbed AND
Thrust bearing
temp < 100 degc AND
Motor
bearing temp. < 85 degc AND
Motor
winding temp. < 125 degc AND
Recirculation valve 40% open
AND
Vent valve
open AND
[[CEP
Standby selected AND Its disch v/v open ]
OR
CEP discharge valve closed ]
2) TRIP PROTECTION
1) Hotwell
Level very low ( < - 1850 mm ) 2/3
2) CEP ON
AND Discharge press. low ( < 18 ksc )
3) CEP ON for
10 sec AND Flow through CEP low ( < 300 tph) TD5s
4) Thrust
bearing temp. very high ( > 105 degc)
5) Motor
bearing temp. very high ( > 90 degc)
6) Motor
winding temp. very high ( > 130 degc)
7) Suction
valve not open
8) Electrical
protection acted
3) AUTO START
1) Pump
Selection Standby AND
Other
Running pump Tripped
2) Pump
Selection Standby AND
Any other
pump ON for 30 sec AND
Discharge
header press. low (<20 ksc)
3) Command from
CEP startup sequence step # 103
4) AUTO STOP
1) Command from
CEP shutdown sequence step # 201
CEP DISCHARGE VALVE
1) AUTO OPEN
1) CEP ON AND
Discharge press. > 18
ksc TD2s
2) CEP
Discharge press. > 18 ksc AND
Any other
CEP ON AND
CEP Standby
Selected TD5s
3) Command from
CEP Startup sequence step # 106
2) OPEN RELEASE
1) Discharge
Valve I.B.V Open
3) CLOSE RELEASE
1) CEP OFF
4) AUTO CLOSE
1) CEP Standby
Selected AND Discharge hdr. press.
< 20 ksc TD2m
2) CEP OFF
3) Command from
CEP Startup sequence step # 102
4) Command from
CEP Shutdown sequence step # 202
5) DISCHARGE VALVE I.B.V AUTO
OPEN
1) CEP ON AND
Discharge press. > 18 ksc TD2s
2) CEP
discharge press. > 18 ksc AND
Any other
CEP ON AND
CEP Standby
Selected TD5s
6) DISCHARGE VALVE I.B.V AUTO
CLOSE
1) Discharge
valve opened
CEP VENT VALVE
1) AUTO OPEN
1) CEP
discharge press. > 18 ksc AND
Any other
CEP ON AND CEP Standby Selected TD5s
2) CEP OFF
3) Command from
CEP Startup sequence step # 103
4) Command from
CEP Shutdown sequence step # 202
2) AUTO CLOSE
1) CEP ON
3) OPEN RELEASE
1) CEP OFF
Comments