TURBINE PROTECTION
1) TG Lub oil
pressure very low (< 1.2 ksc)
3) HP exhaust
temp. high (> 500 degc)
4) Condenser vaccum
low(VSP)
5) Condenser
vaccum low(FSP) (> -0.7 ksc) AND Turbine speed > 240 rpm
6) HP
casing top/btm DT high (> 100 degc) AND Load >100MW
7) IP casing
front top/ btm DT high (> 45 degc)
AND Load >100MW
8) IP casing
rear top/ btm DT high (> 45
degc) AND Load >100MW
9) MFT S/W
& H/W
10) Generator electrical protection S/W &
H/W
11) Liquid in
Generator Main leads top (> 90 mm)
12) Cold gas temp
after cooler A&B high (> 60 degc)
13) Cold gas temp
after cooler C&D high (> 60 degc)
14) Primary water
temp after cooler high (> 71 degc)
15) Seal oil temp
after cooler high (> 55 degc)
16) Hot air main
exciter temp high (> 80 degc)
17) Stator
winding flow very low (< 48 tph)
18) Stator Main
bushing R flow low (< 1.33 tph)
19) Stator Main
bushing S flow low (< 1.33 tph)
20) Stator Main
bushing T flow low (< 1.33 tph)
21) Turbine over
speed trip (electrical) (> 3330
rpm)
22) Turbine over
speed trip H/W
23) Oil tank
level very low ( 1150 mm from top)
24) Turbine trip
from desk operated
25) Turbine trip
from console operated
26) Turbine trip
from ATRS
27) Emergency
trip from HMI
28) Fire
protection 1 or 2 operated
29) Generator
class B protection
30) Low Vacuum
Trip Device operated
31) Manual Trip
Device operated
1.2) ALARM
LIMITS
1) TG Lub oil
pressure very low (< 4.5ksc)
2) Axial shift
high (+/-0.5 mm)
3) HP exhaust
temp. high (> 485 degc)
4) Condenser
vaccum low (FSP) (> -0.8 ksc)
5) HP
casing top/btm DT high (> 90 degc)
6) IP casing
front top/ btm DT high (> 30 degc)
7) IP casing
rear top/ btm DT high (> 30
degc)
8) Cold gas
temp after cooler A&B high (> 55
degc)
9) Cold gas
temp after cooler C&D high (> 55
degc)
10) Stator
winding flow very low (< 54 tph)
11) Stator Main
bushing R flow low (< 1.4 tph)
12) Stator Main
bushing S flow low (< 1.4 tph)
13) Stator Main
bushing T flow low (< 1.4 tph)
14) Turbine over
speed (> 3300 rpm)