Stopping- Starting of 2nd PAPH | |||||||||||||||||
Each unit is provided with two bi-sector type regenerative primary air preheaters to recover the | |||||||||||||||||
heat from waste flue gas leaving from the furnace and utilised to preheat the primary air which inturn | |||||||||||||||||
used to dry the raw coal and transport pulverised coal powder from mill to the furnace through coal pipes. | |||||||||||||||||
Air pre-heater consists mainly rotor housing, cylindrical cellular rotor, guide and Support bearings, oil | |||||||||||||||||
systems for guide and support bearings, soot blower system, Stationary water washing devices & fire | |||||||||||||||||
fighting devices , auxiliary air motor drive with over-running clutch, oil carryover probe , inspection lights s | |||||||||||||||||
etc. The complete rotor is supported by a thrust bearing at the bottom and guided by the radial bearing at | |||||||||||||||||
the upper end. An air motor is provided to ensure the continued operation of the air pre-heater, even if | |||||||||||||||||
power to electric motor is interrupted. It may also be used to control speed of the rotor during water | |||||||||||||||||
washing of heating surfaces. | |||||||||||||||||
When ever one APH trips in a running Unit the run back operates & Unit load gets | |||||||||||||||||
reduced to 300 MW( 60 %) . Normally 4-5 Mill operation permissive is available with one APH out | |||||||||||||||||
of service . | |||||||||||||||||
PROCEDURE FOR STOPPING AND ISOLATION OF ANY SECOND PAPH: - | |||||||||||||||||
E-1 PRE CONDITION OF THE UNIT: - | |||||||||||||||||
1. Unit is running at full load (500MW) with 7 mills in operation. | |||||||||||||||||
2. Both TDBFPs are in service and Feed water control in auto. | |||||||||||||||||
3. MDBFP # C is available on auto (Rapid start up mode). | |||||||||||||||||
4. Unit control is in CMC mode. | |||||||||||||||||
5. Airflow control is in auto with both FD fans in service. | |||||||||||||||||
6. Both PA fans in operation in CAS mode with PA header pressure set at 820mmwc. | |||||||||||||||||
7. Both ID fans in service and furnace draft control in auto. | |||||||||||||||||
E-2 ENSURE THE FOLLOWING: | |||||||||||||||||
1. Running contact of other running PAPH. | |||||||||||||||||
2. Revise the station DC as per the planned shut down programme. | |||||||||||||||||
3. Availability of PAPH / SAPH soot blowers for operation. | |||||||||||||||||
4. Availability of auxiliary drive (air motor) of the PAPH (which is to be stopped). | |||||||||||||||||
5. All (4nos) economizer bypass dampers are closed. | |||||||||||||||||
6. Availability of atomizing steam and HFO at requisite pressure & temp (oil: 100ºC / 17-18 kg/cm², Steam: | |||||||||||||||||
200 – 210ºC / 6.5 kg/cm²). | |||||||||||||||||
7. Completion of WB/LRSB operation before starting the load reduction. | |||||||||||||||||
8. Best communication between control room and local. | |||||||||||||||||
9. Bypass TDBFP – A / B recirculation valve auto-closing protection. | |||||||||||||||||
10. Check for the healthiness of the mill outlet temperature low to feeder tripping protection for all running | |||||||||||||||||
mills, Normally it is set at 50 deg C. | |||||||||||||||||
PAPH STOPPING AND ISOLATION PROCEDURE: - | |||||||||||||||||
1. Take the unit control to manual from CMC mode. (Turbine on limit pressure control and Boiler master on | |||||||||||||||||
manual). | |||||||||||||||||
2. Take fuel master to manual and gradually reduce the load to 400MW by slowly unloading and removing | |||||||||||||||||
7th running mill. Check airflow according to the load (1650T/ hr corresponding to 400MW). | |||||||||||||||||
3. Take HFO support in one elevation corresponding to any running mill according to the mill combination | |||||||||||||||||
(At least 3 oil guns in one elevation). | |||||||||||||||||
4. Gradually reduce the load to 300MW by slowly unloading and removing 6th running mill. Check airflow | |||||||||||||||||
according to the load (1450T/ hr corresponding to 300MW). | |||||||||||||||||
5. Reduce MS pressure set point according to the load during the process of load reduction. | |||||||||||||||||
6. Check the loading and suction flow of TDBFP A / B. If suction flow is low corresponding to the speed, | |||||||||||||||||
Then keep open any one TDBFP- A / B recirculation valve. | |||||||||||||||||
7. Probably keep five consecutive mills in service to ensure stable combustion. | |||||||||||||||||
8. Observe and slowly reduce the PA header pressure set to 800mmwc from 850mmwc. | |||||||||||||||||
9. Adjust the burner tilt position to maintain MS & HRH temperature up to maximum possible (540C). | |||||||||||||||||
10. Gradually close the PAPH (which is to be stopped) air outlet damper from local & lock it mechanically | |||||||||||||||||
and simultaneously maintain the flue gas outlet temperature by closing the FG outlet damper of | |||||||||||||||||
corresponding PAPH. Adjust the other running PAPH & SAPH A/B FG outlet temperature from remote. | |||||||||||||||||
Then isolate the air outlet damper actuator power supply. This activity needs best communication | |||||||||||||||||
between control room and local. | |||||||||||||||||
11. Check the PA header pressure for any variation while closing air outlet damper and adjust it, if required. | |||||||||||||||||
12. Slowly close the air inlet damper from local and lock it mechanically. Isolate the power supply. | |||||||||||||||||
13. Observe the mill outlet temperature and accordingly adjust mill loading. | |||||||||||||||||
14. Close flue gas inlet damper from local and lock it mechanically. Isolate the power supply. | |||||||||||||||||
15. Close flue gas outlet damper from remote fully and lock it mechanically. It can be opened to 10% with the | |||||||||||||||||
help of C& I to create negative draft in side the APH if it is required by BMD. | |||||||||||||||||
16. Observe the mill outlet temperature and APH flue gas outlet temperatures accordingly adjust the running | |||||||||||||||||
PAPH & SAPH – A / B flue gas outlet dampers. | |||||||||||||||||
17. Start running PAPH and SAPH – A / B soot blowing. (This is to be done at least twice in a shift as long as | |||||||||||||||||
oil guns in service). | |||||||||||||||||
18. After stopping the PAPH, Gradually increase the load to approximately 330MW with 5 mills operation by | |||||||||||||||||
observing PA outlet temperature, mill outlet temperature and PA header pressure. | |||||||||||||||||
19. Remove oil support after stabilisation of load at approximately 330MW with 5 mills operation with safe | |||||||||||||||||
mill outlet temperature (Should be >60ºC). | |||||||||||||||||
20. Keep PRAPH in service for attending any work outside the APH like air outlet duct fabric compensator | |||||||||||||||||
repair work. | |||||||||||||||||
21. Stop the PAPH (which is to be stopped) after cooling (air outlet side manhole can be kept open for | |||||||||||||||||
cooling) to normal temperature so that maintenance can be done and isolate the power supply of PRAPH | |||||||||||||||||
drive motor. | |||||||||||||||||
22. Close both main and bypass airlines for air motor. | |||||||||||||||||
23. Press the local EPB of the PAPH (which is stopped). | |||||||||||||||||
24. Issue PFW after ensuring proper isolation according to PFW procedure. | |||||||||||||||||
E-4 PROCEDURE FOR NORMALISATION AND STARTING PRAPH: - | |||||||||||||||||
1. Revise the station DC as per the planned programme. | |||||||||||||||||
2. Ensure the cancellation of PTW and clearance from maintenance BMD/EMD/C&I, then normalise the | |||||||||||||||||
drive motor power supply. | |||||||||||||||||
3. Check the PAPH for proper boxup (check all manholes are closed). | |||||||||||||||||
4. Check the PAPH by running air motor for any abnormal rubbing. | |||||||||||||||||
5. Normalise the drive motor power supply. | |||||||||||||||||
6. Release the local EPB. | |||||||||||||||||
7. Stop PAPH air motor and start main electric motor. | |||||||||||||||||
8. Normalise the air outlet damper power supply. Remove the lock and slowly open the PAPH air outlet | |||||||||||||||||
damper from local. | |||||||||||||||||
9. Normalise the flue gas inlet damper power supply. Remove the lock and slowly open the PAPH flue gas | |||||||||||||||||
inlet damper from local. | |||||||||||||||||
10. Slowly Increase the PA header pressure set point to normal (820mmwc) and wait for stabilisation of the | |||||||||||||||||
header pressure. | |||||||||||||||||
11. Normalise the air inlet damper power supply. Remove the lock and slowly open the air inlet damper from | |||||||||||||||||
local. Simultaneously open flue gas outlet damper from remote and maintain the flue gas outlet | |||||||||||||||||
temperature and observe PA header pressure while opening air inlet damper. | |||||||||||||||||
12. Take 6th mill into service and gradually increase the load to 450MW. | |||||||||||||||||
13. Adjust the MS pressure set point according to the variation of load. | |||||||||||||||||
14. Close TDBFP-A / B recirculation valve (which was kept opened previously) after sufficient loading of both | |||||||||||||||||
TDBFPs. | |||||||||||||||||
15. Take 7th mill into service and increase the load to full (500MW). | |||||||||||||||||
16. Adjust the FG outlet damper positions of PAPH – A / B and SAPH – A / B after stabilization of load. | |||||||||||||||||
17. Adjust the burner tilt to maintain M S & HRH temperature up to maximum possible (540C). | |||||||||||||||||
18. Normalise the TDBFPs recirculation control valve auto close protection. | |||||||||||||||||
19. Put fuel master in auto. | |||||||||||||||||
20. Transfer the unit control from manual to CMC mode. |
Thursday, May 10, 2018
Stopping- Starting of 2nd PAPH
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment