Generator Air Tightness Test |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Period
Of Test= 24 Hrs without a Break |
|
|
|
|
|
|
|
|
|
|
|
Air
Pressure Drop (Allowed in 24 Hrs) : <=0.15 ksc |
|
|
|
|
|
|
|
|
|
Air
Test Pressure = 3.5 ksc |
|
|
|
|
|
|
|
|
|
|
|
|
All
LLDs Drain Closed. |
|
|
|
|
|
|
|
|
|
|
|
|
|
Ensure
Seal Oil system in Operation |
|
|
|
|
|
|
|
|
|
|
|
Seal
Oil DP >1.5 ksc |
|
|
|
|
|
|
|
|
|
|
|
|
|
AS
Seal Oil Pr>4.5 ksc, start H2S Seal Oil system |
|
|
|
|
|
|
|
|
|
|
H2
Cooler Isolated |
|
|
|
|
|
|
|
|
|
|
|
|
|
PW
in Winding is in filled condition, Winding Isolated. PW also kept Isolated. |
|
|
|
|
|
|
PW
Tank at Atmospheric Pressure |
|
|
|
|
|
|
|
|
|
|
|
Ensure
availability of Instrument air and Bleed Out moisture from it by
keeping it open till |
|
|
|
|
|
Connect
flexible air hose with the gas plant through the coupling and ensure no air
leakage is there |
|
|
|
|
The
filling is to be done by opening the valves in the normal H2 filling line
where as the valve from H2 rack side will remain closed. |
Once
the air filling is commenced the test record data sheet |
|
|
|
|
|
|
|
|
The
air valve is to be opened full. |
|
|
|
|
|
|
|
|
|
|
|
While
pressurising the LLD / Seal oil DP / Seal oil parameters are to be recorded
as per the enclosed sheet. |
|
|
|
The
generator casing is to be pressurised with instrument air up to pressure
of 3.5 ksc. |
|
|
|
|
|
The
approximate time to attain rated pressure will be around 7- 8 hrs |
|
|
|
|
|
|
|
Record
the time when the pressure has reached at 3.5 ksc at the special
gauge fixed in the gas rack |
|
|
|
|
Stop
the air filling and shut off the valve when the test pressure has been
reached (3.5bar) and then disconnect the air hose from the system
to avoid further pressurisation of the system. |
Once
the rated pressure has been attained, the test can be commenced. |
|
|
|
|
|
|
|
Once
the test is commenced the test record data sheet is to be filled at hourly
basisfor continuous 24 hrs. No break is allowed. |
During
test ensure the LLD‘s are not getting oil |
|
|
|
|
|
|
|
|
|
|
If
a pressure increase was observed in the primary water tank, a leak of the
primary water system with in the generator would be expected and must be
located and attended |
If
an air loss higher than 0.15 bar/ 24 hrs, a search for leakages must be
made. |
|
|
|
|
|
|
Suspected
areas should be brushed with Diprol or other foaming solution. The formation
of bubbles (foam) indicates a leak. |
|
Attend
the leakages and then repeat the test until satisfactory results are
obtained. |
|
|
|
|
|
|
If
a satisfactory tightness is established the generator may be filled with CO2
and subsequently with H2 as per normal operation practice. |
After
the test is declared complete, the air is to be depressurised and the system
is to be normalised |
|
|
|
After
completion of the test, the electrical purity meter system should be
calibrated with pure CO2 and H2 |
|
|
|
Normalise
the primary water coolers and take the primary water system into service. |
|
|
|
|
|
Normalise
the all-4 hydrogen coolers |
|
|
|
|
|
|
|
|
|
|
|
Then
the generator may be filled with CO2 and subsequently with H2 as per normal
procedure. |
|
|
|
|
Comments
Post a Comment