220V DC FAILURE
220V DC FAILURE
IDENTIFICATION:
- Boiler and Turbine will trip.
- 220V DC failure alarm will appear in facia & DCDB voltage will read 0V
- Generator will start motoring & motoring alarm will appear.
- Boiler will trip on “220V DC failure” protection by FSSS.
- HOTV & LOTV will close.
- All running mills CAD’S & HAG’S will close.
- All running mills feeders will trip.
- SADC will full open.
- All HT (11kv & 3.3kv) drives will continue to run.
- All mills, PA fans, CC pumps, ID&FD fans will continue to run.
- Turbine will trip on boiler trip protection through MFT.
- all stop valves & control valves will close.
- TDBFP A&B will trip.
- MDBFP if not in service will not take start.
- Extraction FC NRV will close.
- Vacuum breaker remains close.
- Generator will start motoring & will not trip (All electrical protection will not work)
- Field breaker inoperative.
- All HT breakers protection is not available.
- All DC oil pumps & scanner air fan are not available.
- Generator breaker DC is from SY hence Breaker is operable from UCB but “DO NOT OPEN GEN BREAKER”. This will cause:
- BA,BB & CA bus dead as UT to station change over will not takes place.
- All critical equipments AOPS, JOP, Seal oil pump, AC scanner air fan Power supply will not be available.
- Start DG set from UCB.(DG set control supply (DC) is not available)
- Rush to local, trip emergency SWGR normal incomer breaker & close tie from DG set
- Trip UT incomer breaker from local.
- Start TG AOP#2, TDBFP’sAOP#2, and seal oil pump #2 from UCB.
- AC scanner air fan will continue to run.
- Trip generator breaker.
- Switch off De-excitation switch at AVR panel.
- Switch off field breaker from AVR panel.
- Start jop#1 at TG speed of 510 RPM.
- Restore DC as quick as possible.
Comments
Post a Comment