MS/HRH TEMPERATURE RISING/FALLING FAST
MS TEMPERATURE RISING FAST
Plant response
Likely causes
Likely causes
Plant response
Likely causes
Plant response
Parameters of concern/Adverse effects
Likely causes
· Inadequate spray due to malfunctioning of spray control valves.
· Excess airflow.
· Burner tilt stuck in up position
· Leakage in the spray line.
· Low feed water temperature.
· Boiler firing raised in top elevation
· Heavy furnace slagging
· Spray isolation valve in close condition
Plant response
· MS temperature high alarm will appear.
· Spray control valves will go for further opening.
· If temperature is very high, turbine will trip.
Parameters of concern/Adverse effects
· MS/RH temperatures
· MS temp at turbine inlet
· HP exhaust temperature.
· Spray quantity/ FCV differential pressure.
· Tilt position
· Metal temp. raise above design value will reduce tube life drastically
Immediate expected or desirable operator action
· Make burner tilt fully down
· Take MS spray control to manual & raise spray quantity
· Reduce firing in top elevation
· If rate of pressure rise is more, then pick up load if margin is there.
· Reduce airflow based on the O2 percentage.
· Check spray station is properly lined up
Final correction activity
· Start soot blowing, if slagging is more
· Restore back the temp controls in auto if it has been taken in manual
· Check for any malfunction of spray control valves & isolate such type of valve.
· Burner tilt can be kept horizontal.
9. RH TEMPERATURE RISING FAST
Likely causes
· Inadequate spray due to malfunctioning of spray control valves.
· Excess airflow.
· Burner tilt stuck in up position
· Leakage in the spray line.
· Low feed water temperature.
· Boiler firing raised in top elevation
· Heavy furnace slagging
· HP exhaust temp is high
· Spray isolation valve in close condition
Plant response
· RH temperature high alarm will appear.
· Amount of spray will rise.
· Turbine will trip if RH temp reaches very high
Parameters of concern/Adverse effects
· RH temperatures
· RH temp at turbine inlet
· HP exhaust temperature.
· Spray quantity/ FCV differential pressure.
· Tilt position
· Metal temp raise above design value will reduce tube life drastically
Immediate expected or desirable operator action
· Make burner tilt fully down
· Take RH spray control to manual & raise spray quantity
· Reduce firing in top elevation
· If rate of pressure rise is more, then pick up load if margin is there.
· Reduce airflow based on the O2 percentage.
· Check spray station is properly lined up
· Check HP exhaust temp is normal
Final correction activity
· Start soot blowing if furnace slagging is there.
· Keep the burner tilt in horizontal condition.
· Restore back the control in auto if it has been taken in manual.
10. MS TEMPERATURE FALLING FAST
Likely causes
· Tripping of mill
· Sudden boiler pressure drop
· Malfunctioning of spray control valves.
· Spray station passing
· Less air flow
· Burner tilt fully down
· High feed water temperature
· Soot deposits on SH tubes
Plant response
· MS temperature low alarm will appear.
· Turbine will trip if MS temp goes very low.
Parameters of concern/Adverse effects
· Ms temp
· Spray quantity
· Burner tilt
Immediate expected or desirable operator action
· Close the spray control valves by taking it into manual.
· Make burner tilt upward.
· Check airflow &Rise if necessary.
· Increase firing in top elevation
· Reduce turbine load if pressure is dropping
· Close spray station Block valve/ isolation valve if control valve is passing.
Final correction activity
· Start LRSB operation
· Observe for improvement in temperature.
· Restore back the controls in auto (spray control)
· Check for any malfunction of control valve & isolate it.
11. RH TEMPERATURE FALLING FAST
Likely causes
· Tripping of mill
· Sudden boiler pressure drop
· Malfunctioning of spray control valves.
· Spray station passing
· Less air flow
· Burner tilt fully down
· High feed water temperature
· Soot deposits on RH tubes
Plant response
· RH temperature low alarm will appear.
Parameters of concern/Adverse effects
· RH temp
· Spray quantity
· Burner tilt
· Load
Immediate expected or desirable operator action
· Close the spray control valves by taking it into manual
· Make burner tilt upward
· Check airflow &Rise if necessary
· Increase firing in top elevation
· Reduce turbine load if pressure is dropping
· Close spray station Block valve/ isolation valve if control valve is passing.
Final correction activity
· Start LRSB operation
· Observe for improvement in temperature.
· Restore back the controls in auto (spray control)
· Check for any malfunction of control valve & isolate it.