Feeder COC Not running

Feeder COC Not running

  • Reduce load of the Feeder up to 20 TPH
  • Send Operator to close Feeder inlet chain gate
  • As Feeder supply of coal is been cut, feed rate will decrease to 0
  • Feeder will Trip on No coal flow, if not Trip the Feeder.
  • Send operator to Open the mill reject.
  • Wait till the Mill current comes to No load current.
  • Slowly reduce the air flow to zero by regulating CAD.
  • Trip the Mill
  • Close the Feeder seal air valve and Feeder Outlet valve. If not, inform C&I personnel to do so.
  • Isolate Feeder power supply from switch-gear and lock the module.
  • Raise Job card in SAP