CRE-9 Both DPU Failed

CRE-9 

  • PA Header Control
  • BCW-C OLCS
  • CMC Logic
  • Metal Temp SH, RH
  • Economiser Bypass Damper control
What happens when Both DPU failed?

  • PA Header Pressure Bad/ PA Header control Parameters Bad
  • BCW-C  Parameters Bad
  • CMC Logic out
  • Metal Temp Bad
  • Eco Bypass Damper Control Bad
What To do?

  • Take Machine in Hydraulic mode and Isolate EHTC from Rack
  • Isolate PA fan Blade-pitch supply from Switch-gear or actuator Control to Manual/OFF from local
  • Take CB of BCW-C in switchgear mode from switchgear
  • Now Call the C&I Personnel to force PA Header Pressure Transmitter value(T1,T2, T3) to near the freeze value that is 820 mm WC
  • Give healthy value to PA Hdr Pressure selector (Putting ! before each xmtr value )in Header control tag
  • Now Rectify DPU Problem/ Reset it
  • Ensure both DPU working fine
  • Now Normalise Both PA fan BLade Pitch from local/Switchgear
  • Modulate Blade-pitch of both PA fans  
  • Put Blade-Pitch on auto and Control in Auto too
  • Normalise BCW-c from switchgear
  • Put machine in EHG by normalising from local rack
  • Put machine in CMC 